Inhouse product
| Main Feature | ||
| Capacity | 3KVA/3KW | |
| Display Type | 2×8PIN/Pitch2.54mm, supports 128-bit segment code, up to 4 buttons + 4 LEDs, can display operating mode/load / input/output, etc. | |
| Load Capacity | AC mode: 30min@102%~110% Load; 10min@110%~130% Load; 30s@130%~150% Load; 200ms@>150% Load Battery mode: 10min@102%~110% Load; 1min@110%~130% Load; 10s@130%~150% Load; 200ms@>150% Load | |
| Input Voltage | 208/220/230/240VAC | |
| Output Voltage | 208/220/230/240VAC | |
| Noise Level | ≤45db | |
| Battery | Battery type: Lead Acid Battery Rated Battery Voltage: 96V Battery Spec: 8*12V/7Ah Number of Internal Battery: 6/8(optional) | |
| Others | With double conversion online design, zero output transfer time. Adopt DSP digital control Adopt the technology of active power factor correction technology (PFC) With 3-5 minutes can work when on full loads. Cold start by battery without grid Input. | |
| Input Features | ||
| Frequency | 50/60±6Hz (Default), ±10Hz (Settable) | |
| Power Factor | L+N+PE | |
| Voltage Range | 110~300VAC | |
| Output Features | ||
| Voltage Range | 208/220/230/240VAC | |
| Power Factor | L+N+PE | |
| Transfer Time | 4ms | |
| Physical Specification | ||
| Dimension | 192*326*397mm | |
| Weight | 24 kg | |
| Manufacture Warranty | ||
| Warranty | 1 Year (Box Mandatory While Claiming) Under the following conditions, the warranty would not be provided: • UPS burning due to thunder, abnormal overload, insect entrance and others. • If ambient temperature should not be maintained at 20 to 26 degrees Celsius with proper dehumidification. (24/7) • If the product is placed in a dusty and damp place. • In the absence of Generator connectivity Without proper battery charge, the warranty will be void. • Battery swelling and overcharging due to the wrong system voltage setting of the UPS. | |