| Main Feature | ||
| Capacity | 6000 VA | |
| Display Type | LCD Display | |
| Load Capacity | 5400 W | |
| Input Voltage | Nominal Voltage: 208/220/230/240 VAC Input voltage range: 110-300 VAC (Based on load at 50%); 176-300VAC (Based on load at 100%) | |
| Output Voltage | 208/220/230/240V AC AC Voltage Regulation: ±1% | |
| Frequency (Battery Mode) | 50 Hz or 60Hz ± 0.1 Hz | |
| Noise Level | 55dB @ 1 Meter | |
| Battery | Battery Numbers: 16 ~ 20 Charging Current: Default 4A. Settable to 1/2/4/6 A (6A available for 16 number of batteries only*) Charging Voltage: 218 Vdc +/- 1% (Based on 16pcs batteries) | |
| Alarm | Battery Mode: Sounding every 4 seconds Low Battery: Sounding every second Overload: Sounding twice every second Fault: Continuously sounding | |
| Indications | LCD: Panel UPS status, load level, battery level, input/output voltage, discharge timer, and fault conditions | |
| Others | Environment Operation Humidity: 0-95 % & non-condensing Operation Temperature: 0~40 deg.C Operation Altitude: <1000 m Noise Level Less than 55dB @ 1 Meter Management: Smart RS-232 or USB: Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC Intelligent Slot for Optional cards: Power monitoring though SNMP/ Modbus/ Dry Contacts | |
| Input Features | ||
| Frequency | 46Hz ~ 54 Hz or 56 ~ 64 Hz | |
| Power Factor | ≥ 0.99 @ 100% load | |
| Voltage Range | Nominal Voltage: 208/220/230/240 VAC Input voltage range: 110-300 VAC (Based on load at 50%); 176-300VAC (Based on load at 100%) | |
| Output Features | ||
| Voltage Range | 208/220/230/240VAC | |
| Power Factor | 0.9 | |
| Type of Wave | Pure Sine wave | |
| Transfer Time | Transfer Time: Bypass to Inverter (Line mode): Zero Transfer Time: Inverter to Bypass (Line mode): 4 millisecond (ms) (Typical) | |
| Manufacture Warranty | ||
| Warranty | 1 Year (UPS), 6 Months (Battery) Under the following conditions, the warranty would not be provided: • UPS burning due to thunder, abnormal overload, insect entrance and others. • If ambient temperature should not be maintained at 20 to 26 degrees Celsius with proper dehumidification. (24/7) • If the product is placed in a dusty and damp place. • In the absence of Generator connectivity Without proper battery charge, the warranty will be void. • Battery swelling and overcharging due to the wrong system voltage setting of the UPS. | |